6242Y and 6243Y are single-core, PVC-insulated copper cables designed for internal wiring of appliances, control systems, and light industrial equipment. Compliant with VDE standards (EN 50525-3-11) and widely used in European markets.
Parameter | 6242Y | 6243Y |
---|---|---|
Rated Voltage | 300/500V | 300/500V |
Temperature Range | -5°C to +70°C (fixed installation) | -5°C to +90°C (fixed installation) |
Conductor | Bare copper or tinned copper | Bare copper or tinned copper |
Insulation Material | PVC (Type Y) | Heat-resistant PVC (Type Y) |
Standards | VDE, CE, RoHS, REACH | VDE, CE, RoHS, REACH |
Flame Retardancy | IEC 60332-1-2 | IEC 60332-1-2 |
Conductor Size (mm²) | Stranding | Insulation Thickness (mm) | Overall Diameter (mm) |
---|---|---|---|
0.5 | 16/0.20 | 0.6 | 2.8 ±0.1 |
0.75 | 24/0.20 | 0.6 | 3.0 ±0.1 |
1.0 | 32/0.20 | 0.7 | 3.4 ±0.1 |
1.5 | 30/0.25 | 0.7 | 3.8 ±0.1 |
2.5 | 50/0.25 | 0.8 | 4.4 ±0.1 |
Voltage Test: 2000V AC for 5 minutes (no breakdown).
Insulation Resistance: ≥20 MΩ·km at 20°C.
Bending Radius: ≥4× cable diameter.
Color Coding: Available in standard colors (black, brown, blue, green/yellow) or custom options.
Internal wiring of household appliances (e.g., washing machines, ovens).
Control panels, lighting systems, and industrial machinery.
Fixed installations in dry or damp environments (non-outdoor use).
Compliance: EN 50525-3-11, IEC 60227, RoHS Directive.
Certification Marks: VDE, CE, UKCA.
Standard length: 100m/coil or 500m/drum.